Tabel B.52.5

Strømværdier i ampere for installationsmetoder i tabel B.52.1 – XLPE-/EPR-isolering/tre belastede ledere, kobber eller aluminium

Nominelt leder-tværsnit mm² Installationsmetode i tabel B.52.1
A1 A2 B1 B2 C D1 D2
1 2 3 4 5 6 7 8
Kobber
1,51716,52019,5222123
2,523222826302830
431303735403639
640384844524449
1054516660715865
1673688880967584
25958911710511996107
35117109144128147115129
50141130175154179135153
70179164222194229167188
95216197269233278197226
120249227312268322223257
150285259347300371251287
185324295384340424281324
240380346450398500324375
300435396514455576365419
Aluminium
2,5191822212422-
4252429283228-
6323138354135-
10444152485746-
1658557164765964
2576719384907582
3594871161031129098
50113104140124136106117
70142131179156174130144
95171157217188211154172
120197180251216245174197
150226206267240283197220
185256233300272323220250
240300273351318382253290
300344313402364440286326

NOTE 1: I kolonne 3, 5, 6, 7 og 8 er det antaget, at ledere er runde for tværsnit til og med 16 mrf. Værdier for større tværsnit gælder for sektorformede ledere og kan med sikkerhed anvendes for runde ledere.